Compressed air fail: Ventilation design

December 23, 2022 By Paul Heney

Share
Fig.1. These air-cooled compressors are running hot, loading the associated air dryers excessively because the ventilation designer did not address all the sources of heat in the room and the source of the cooling air.

A plastics manufacturer was having constant trouble with his desiccant air dryers. No matter what he did, they would constantly set off dewpoint alarms, which was very annoying. He called in a compressed air auditor to have a look.

The auditor shot temperatures and found that the discharge of the compressors was too hot. Outputs exceeding 120° F contained more water than the air dryers were rated to process, with moisture levels increasing by about double for every 20° F increase. The auditor measured the temperature of the cooling air, this was also excessive, even though the temperature outdoors was only 30° F.

The auditor pointed to the compressor room ventilation inlet duct — it was coming from the plant, where temperatures were near 90° F. He directed the Maintenance Manager’s attention to two electric vacuum pumps in the room that were radiating significant amounts of heat. And he pointed up to the hot air ducting that was connected to the compressor. The large hot surfaces were radiating a significant amount of heat into the room, raising the ventilation air temperature to excessive levels.

The ventilation system designer had not accounted for all sources heat radiation within the room, had chosen a poor source of cooling air, and had no cross ventilation. The compressors were overheating because the cooling air was too hot, overloading the air dryers. Clearly, this was the cause of the constant alarms.

At this site, it was relatively easy to install additional ventilation with thermostatic control to temper the room with cool outside air, but not to subject equipment to freezing winter temperatures. Once this was in place, the Maintenance Manager finally had peace again.

 

 

You may also like:


  • Compressed air fail: Fire system

  • Compressed air fail: Dryer signature

  • Compressed air fail: Wet flow

  • Compressed air fail: Draining profits

Filed Under: Air Compressors, Air Preparation, Blog

Primary Sidebar

Fluid Power World Digital Edition

Fluid Power World Digital EditionBrowse the most current issue of Fluid Power World and back issues in an easy to use high quality format. Bookmark, share and interact with the leading design engineering magazine today.

RSS Featured White Papers

  • eBook: Practical Guide to Pneumatics
  • Saving energy and service cost with electric linear systems
  • White Paper-How to Design Efficient Pneumatic Systems!

Fluid Power Design Guides

fluid
“pt
EXPAND YOUR KNOWLEDGE AND STAY CONNECTED
Get the latest info on technologies, tools and strategies for Fluid Power Professionals.
Hose Assembly Tips

Footer

Pneumatic Tips

Fluid Power World Network

  • Fluid Power World
  • Hose Assembly Tips
  • Mobile Hydraulic Tips
  • Sealing and Contamination Tips
  • Fluid Power Distributor Lookup

PNEUMATIC TIPS

  • Subscribe to our newsletter
  • Advertise with us
  • Contact us
  • About us

Copyright © 2026 · WTWH Media LLC and its licensors. All rights reserved.
The material on this site may not be reproduced, distributed, transmitted, cached or otherwise used, except with the prior written permission of WTWH Media.

Privacy Policy